1/8 DIN Fuzzy Logic Digital Indicator Controller 
   
   The FuzyPro 1/8 DIN Fuzzy Logic Digital Indicator Controller Model 8010 available with red or green displays. One latchable relay is fitted as standard, plug-in modules allow two more alarm relays, PV retransmission or transmitter PSU. 
  
  
  - 
  
Four-digit LED display  
  - 
  
Up to 3 alarms  
  - 
  
transmitter PSU option  
  - 
  
Min/max value hold  
  - 
  
Engineering units  
  - 
  
PC configuration  
  - 
  
PV retransmit option  
  - 
  
RS485 comms option  
   
   
  
  
  
  
1/8 DIN Fuzzy Logic Digital Indicator Controller Features: 
  
  
  | 
   Output Configuration 
   | 
  
   Up to 3 total, max 3 for Alarms, max 1 for retransmit of PV, max 1 transmitter power supply 
   | 
   
  
  | 
   Alarm 1, 2 & 3 Types 
   | 
  
   Process high, process low, direct acting, process high, process low reverse and logical OR 
   | 
   
  
  | 
   Viewable Values 
   | 
  
   Process variable, maximum value, minimum value and elapsed time since reset 
   | 
   
  
  | 
   Legends 
   | 
  
   ºC/ºF LED, Labels for 27 other common units, mounted behind clear window 
   | 
   
  
  | 
   Human Interface 
   | 
  
   3 button operation, 4 digit 13 mm high red or green display, plus setup, alarm, max & min indicators 
   | 
   
  
  | 
   PC Configuration 
   | 
  
   Off-line configuration from serial port to dedicated config socket (comms option not required) 
   | 
   
   
    
  1/8 DIN Fuzzy Logic Digital Indicator Controller Input: 
  
  
  | 
   Thermocouple 
   | 
  
   J, K, R, S, T, B, L, & N 
   | 
   
  
  | 
   RTD 
   | 
  
   3 wire PT100 50  per lead maximum (balanced) 
   | 
   
  
  | 
   DC Linear 
   | 
  
   0-20/4-20mA, 0-50/10-50mV, 0-5/1-5/0-10/2-10V. Scalable -1999 to 9999, dec point available 
   | 
   
  
  | 
   Impedance 
   | 
  
   >100M  for Thermocouple and mV ranges, 47K  for V ranges and 4.7  for mA ranges 
   | 
   
  
  | 
   Accuracy 
   | 
  
   +/- 0.25% of input scan +/- 1 LSD (T/C CJC better than 0.7ºC) 
   | 
   
  
  | 
   Sampling 
   | 
  
   4 per second, 14 bit resolution approximately 
   | 
   
  
  | 
   Sensor Break Detection 
   | 
  
   <2 secs (except zero based DC ranges), *high alarms activate (*low for RTD, mA or V) 
   | 
   
   
    
  1/8 DIN Fuzzy Logic Digital Indicator Controller Outputs & Options: 
  
  
  | 
   Alarm 1 Relay 
   | 
  
   Contact SPDT 2Amp resistive at 240V AC, >500,000 operations, latching or non-latching. Fitted as standard 
   | 
   
  
  | 
   Alarm 2 & 3 Relays 
   | 
  
   Contacts SPDT 2 Amp resistive at 240V AC, >500,000 operations (optional) 
   | 
   
  
  | 
   Retransmit Output 
   | 
  
   0-20/4-20mA to 500  max, 0-10/0-5V into 500  min. Accuracy typically +/- 0.25% 
   | 
   
  
  | 
   Transmitter Power Supply 
   | 
  
   20-28V DC (24V nominal), max load 910  (22mA at 20V) 
   | 
   
  
  | 
   Remote Reset 
   | 
  
   External reset of latching alarm 1 relay. Volt free or TTL input (Reset = open to close or "0" to "1" transition. 0 = -0.6 to 0.8V, 1 = 2 to 24V) 
   | 
   
  
  | 
   Communications 
   | 
  
   2 wire RS485, 1200 to 9600 baud. Modbus or West ASCII (selectable) 
   | 
   
   
    
  1/8 DIN Fuzzy Logic Digital Indicator Controller Operating & Environmental: 
  
  
  | 
   Temperature & RH 
   | 
  
   0 to 55ºC (-20 to 80ºC storage), 20% to 95% RH non-condensing 
   | 
   
  
  | 
   Power Supply 
   | 
  
   100 to 240V 50/60Hz (optional 20 to 55V AC/22 to 65V DC), approx 4 Watts 
   | 
   
  
  | 
   Front Panel Protection 
   | 
  
   IEC IP66 (Behind panel protection is IP20) 
   | 
   
  
  | 
   Approvals and Certification 
   | 
  
   CE, UL & ULc 
   | 
   
   
    
   